CyberPower OLS1000EA uninterruptible power supply (UPS) Double-conversion (Online) 1 kVA 900 W 3 AC outlet(s)
<
>
Images are illustrative. The product shown may differ from the one offered or include components not part of the product set.
VendorCyberPower
Product codeOLS1000EA-DE
Warranty
2 years
Price€264.80
Price (excl. VAT)€213.55
Availability5+ pcs
Ships out in4-7 bd
Input frequency:
50/60 Hz
Output operation voltage (min):
208 V
UPS topology:
Double-conversion (Online)
Output voltage Total Harmonic Distortion (THD):
3%
Output power capacity:
1 kVA
Input power factor:
0.98
EMI/RFI noise filtering:
Yes
Output frequency:
50/60 Hz
Output power factor:
0.9
Efficiency (ECO mode):
95%
Crest factor:
3:1
Maximum current:
4.5 A
Output operation voltage (max):
240 V
ECO mode:
Yes
Emergency Power Off (EPO):
Yes
Audible alarm modes:
Battery replacement, Fault, Overload alarm
Surge energy rating:
345 J
Input operation voltage (max):
300 V
Waveform:
Pure sine
Input operation voltage (min):
160 V
Response time:
0 ms
Power protection features:
Overload
Output power:
900 W
Audible alarm(s):
Yes
Display type:
LCD
Built-in fan:
Yes
Form factor:
Tower
Housing material:
Metal
Cable length:
1.5 m
Product colour:
Black
Non-operating altitude:
0 - 1500 m
Storage temperature (T-T):
-20 - 50 °C
Operating relative humidity (H-H):
20 - 90%
Storage relative humidity (H-H):
10 - 90%
Operating altitude:
0 - 1500 m
Operating temperature (T-T):
0 - 40 °C
Depth:
327 mm
Height:
191 mm
Weight:
9.4 kg
Width:
140 mm
Cables included:
USB cable
Manual:
Yes
Compliance certificates:
RoHS, CE
AC outlet types:
IEC 320
USB port:
Yes
Power plug:
C13 coupler
AC outlets quantity:
3 AC outlet(s)
Typical backup time at half load:
11 min
Charging current:
1.5 A
Battery life (max):
4 year(s)
Typical backup time at full load:
4 min
Battery technology:
Sealed Lead Acid (VRLA)
Harmonized System (HS) code:
8504408590
Warnings:
Use the appliance in well-ventilated areas to avoid overheating., Keep away from sources of fire and water., Do not disassemble the unit housing, there may be a risk of electric shock.